;/* VEGA Grieshaber KG */
;/* Am Hohenstein 113 */
;/* 77761 Schiltach */
;/* -Germany- */
;/* Phone: +49783650-0 */
;/***************************************************************************/
;/* */
;/* GSD-File fuer VEGAPULS 66 */
;/* */
;/***************************************************************************/
;/* Autor: R. Schaetzle Edit: K. Guenter */
;/* GSD-File-Version: 1.2 */
;/* GSD-Revision: 4 */
;/* Datum: 15.01.2009 */
;/* geaendert am: 19.05.2011 */
;/* */
;/* geaendert am: 01.02.2012 */
;/* weitere Baudraten f<>r SK2/SK3 hinzu */
;/* Min_Slave_Intervall = 6, geaendert f<>r SK2/SK3 */
;/* Model_Name geaendert (ohne DevRev 1) */
;/* Revision geaendert in "Profil 3.02" */
;/* */
;/* File-Name: PS660C00.GSD */
;/***************************************************************************/
;/***************************************************************************/
;/* General DP-Key Words */
;/***************************************************************************/
#Profibus_DP
GSD_Revision = 4
Vendor_Name = "VEGA Grieshaber KG"
Model_Name = "VEGAPULS 66"
Revision = "Profil 3.02"
Ident_Number = 0x0c00
Protocol_Ident = 0 ; Profibus-DP
Station_Type = 0 ; DP-Slave
FMS_supp = 0
Hardware_Release = "-"
Software_Release = "-"
;
31.25_supp = 1 ; PA-Baudrate
45.45_supp = 1 ; Siemens Segmentcoupler
93.75_supp = 1 ; Pepperl & Fuchs Segmentcoupler
187.5_supp = 1 ; SK2/3
500_supp = 1 ; SK2/3
1.5M_supp = 1 ; SK2/3
3M_supp = 1 ; SK2/3
6M_supp = 1 ; SK2/3
12M_supp = 1 ; SK2/3
;
MaxTsdr_31.25 = 100 ; PA-Baudrate
MaxTsdr_45.45 = 250 ; Siemens Segmentcoupler
MaxTsdr_93.75 = 1000 ; Pepperl & Fuchs Segmentcoupler
MaxTsdr_187.5 = 60 ; SK2/3
MaxTsdr_500 = 100 ; SK2/3
MaxTsdr_1.5M = 150 ; SK2/3
MaxTsdr_3M = 250 ; SK2/3
MaxTsdr_6M = 450 ; SK2/3
MaxTsdr_12M = 800 ; SK2/3
;
Redundancy = 0
Repeater_Ctrl_Sig = 0
24V_Pins = 0
Implementation_Type = "SPC4-2 / TMG i-tec"
Bitmap_Device = "P660C00N"
Bitmap_Diag = "P660C00D"
Bitmap_SF = "P660C00S"
;
;--- Description of physical interface for async. and sync. transmission ---
Physical_Interface = 1 ; IEC61158-2
Transmission_Delay_31.25 = 0
Reaction_Delay_31.25 = 0
End_Physical_Interface
;
Physical_Interface = 0 ; RS-485 Standard Copper
Transmission_Delay_45.45 = 0
Reaction_Delay_45.45 = 0
Transmission_Delay_93.75 = 0
Reaction_Delay_93.75 = 0
Transmission_Delay_187.5 = 0
Reaction_Delay_187.5 = 0
Transmission_Delay_500 = 0
Reaction_Delay_500 = 0
Transmission_Delay_1.5M = 0
Reaction_Delay_1.5M = 0
Transmission_Delay_3M = 0
Reaction_Delay_3M = 0
Transmission_Delay_6M = 0
Reaction_Delay_6M = 0
Transmission_Delay_12M = 0
Reaction_Delay_12M = 0
End_Physical_Interface
;
;
;/***************************************************************************/
;/* Basic DP-Slave related key words */
;/***************************************************************************/
Freeze_Mode_supp = 1 ; Note: Freeze mode is not supported when using SK2/SK3
Sync_Mode_supp = 0
Auto_Baud_supp = 0
Set_Slave_Add_supp = 1
;
Max_User_Prm_Data_Len = 8 ;DPV1_Status1...3 and profile specific Prm_Structure (size = 5 bytes)
;
PrmText=1
Text(0)="Disabled" ;classic diagnosis and status mode
Text(1)="Enabled" ;condensed diagnosis and status mode
EndPrmText
;
ExtUserPrmData=1 "Condensed Status"
Bit(0) 1 0-1 ;PRM_COND
Prm_Text_Ref=1 ;reference to PrmText
EndExtUserPrmData
;
Ext_User_Prm_Data_Const(0)=0x00,0x00,0x08,0x05,0x41,0x00,0x00,0x01 ;DPV1_Status1...3 and profile specific Prm_Structure (default values)
; Structure_Length = 5
; Structure_Type = 65 (profile specific)
; Slot_Number = 0
; reserved = 0
; PRM_COND = 1 (enabled)
;
Ext_User_Prm_Data_Ref(7)=1 ;reference to condensed status bit PRM_COND
Prm_Block_Structure_supp=1 ;enables the block structure of extended parametrization
;
;
Min_Slave_Intervall = 6 ;Time base 100<30>s, modified for applications with SK2/SK3
;
Modular_Station = 1
Max_Module = 3
Max_Input_Len = 15
Max_Output_Len = 0
Max_Data_Len = 15
Max_Diag_Data_Len = 20
;
;Profile specific diagnosis flags
Unit_Diag_Bit(16) = "Status appears"
Unit_Diag_Bit(17) = "Status disappears"
Unit_Diag_Bit(24) = "Hardware failure electronics"
Unit_Diag_Bit(25) = "Hardware failure mechanics"
Unit_Diag_Bit(26) = "Motor temperature too high"
Unit_Diag_Bit(27) = "Electronic temperature too high"
Unit_Diag_Bit(28) = "Memory error"
Unit_Diag_Bit(29) = "Measurement failure"
Unit_Diag_Bit(30) = "Device not initialized"
Unit_Diag_Bit(31) = "Device initialization failed"
Unit_Diag_Bit(32) = "Zero point error"
Unit_Diag_Bit(33) = "Power supply failed"
Unit_Diag_Bit(34) = "Configuration invalid"
Unit_Diag_Bit(35) = "Warmstart"
Unit_Diag_Bit(36) = "Coldstart"
Unit_Diag_Bit(37) = "Maintenance required"
Unit_Diag_Bit(38) = "Characterization invalid"
Unit_Diag_Bit(39) = "Ident number violation"
Unit_Diag_Bit(40) = "Maintenance alarm"
Unit_Diag_Bit(41) = "Maintenance demanded"
Unit_Diag_Bit(42) = "Function check"
Unit_Diag_Bit(43) = "Invalid process conditions"
Unit_Diag_Bit(55) = "Extension available"
;
;Manufacturer specific diagnosis flags
Unit_Diag_Bit(56) = "No measured value available Err"
Unit_Diag_Bit(57) = "Adjusted span too small"
Unit_Diag_Bit(58) = "Error in linearization chart"
Unit_Diag_Bit(59) = "No executable firmware"
Unit_Diag_Bit(60) = "Failure in electronics"
Unit_Diag_Bit(61) = "General software error"
Unit_Diag_Bit(62) = "Measured value is determined"
Unit_Diag_Bit(63) = "Impermissible electronics temp."
Unit_Diag_Bit(64) = "Error in calibration"
Unit_Diag_Bit(65) = "Error in device settings"
Unit_Diag_Bit(66) = "Installation/setup error"
Unit_Diag_Bit(67) = "Measurement malfunction"
Unit_Diag_Bit(68) = "Communication hardware error"
Unit_Diag_Bit(69) = "Factory settings invalid"
Unit_Diag_Bit(70) = "Error in inactive linearization"
Unit_Diag_Bit(71) = "Event storage malfunction"
Unit_Diag_Bit(72) = "Reliability too low"
Unit_Diag_Bit(73) = "Error on a device interface"
Unit_Diag_Bit(74) = "Device temperature out of spec"
Unit_Diag_Bit(75) = "Simulation active"
Unit_Diag_Bit(76) = "Overfilling"
Unit_Diag_Bit(77) = "No measured value available Warn"
;
Unit_Diag_Bit(88) = "Sensor value simulated"
Unit_Diag_Bit(89) = "Sensor value invalid"
Unit_Diag_Bit(90) = "Sensor value limited"
Unit_Diag_Bit(92) = "Percent value simulated"
Unit_Diag_Bit(93) = "Percent value invalid"
Unit_Diag_Bit(94) = "Percent value limited"
Unit_Diag_Bit(96) = "Lin percent value simulated"
Unit_Diag_Bit(97) = "Lin percent value invalid"
Unit_Diag_Bit(98) = "Lin percent value limited"
;
;/***************************************************************************/
;/* Module definition */
;/***************************************************************************/
;--- Module for Analog Input 1 -------------------------------------------------
Module = "AI FB1 (OUT, short)" 0x94
1
EndModule
;
Module = "AI FB1 (OUT, long)" 0x42,0x84,0x08,0x05
2
EndModule
;
;--- Module for Analog Input 2 -------------------------------------------------
Module = "AI FB2 (OUT, short)" 0x94
3
EndModule
;
Module = "AI FB2 (OUT, long)" 0x42,0x84,0x08,0x05
4
EndModule
;
;--- Module for Analog Input 3 -------------------------------------------------
Module = "AI FB3 (OUT, short)" 0x94
5
EndModule
;
Module = "AI FB3 (OUT, long)" 0x42,0x84,0x08,0x05
6
EndModule
;
;--- Empty module --------------------------------------------------------------
Module = "Free Place" 0x00
7
EndModule
;
;
Slave_Family = 12@VEGA@VEGAPULS ;PA-Device-VEGA-directory
Info_Text = "PROFIBUS-PA device according to Profibus-PA-Profile 3.02"
;
;/***************************************************************************/
;/* Additional keywords for module assignment */
;/***************************************************************************/
SlotDefinition
Slot(1) = "AI FB1 (OUT)" 2 1,2,7
Slot(2) = "AI FB2 (OUT)" 4 3,4,7
Slot(3) = "AI FB3 (OUT)" 6 5,6,7
EndSlotDefinition
;
;
;/***************************************************************************/
;/* Slave related keywords for DP extensions */
;/***************************************************************************/
DPV1_Slave = 1
C2_Read_Write_supp = 1
C2_Read_Write_required = 1
C2_Max_Data_Len = 72
C2_Max_Count_Channels = 3
Max_Initiate_PDU_Length = 52
C2_Response_Timeout = 4000 ;Timebase 10ms
DPV1_Data_Types = 1
WD_Base_1ms_supp = 1