You cannot select more than 25 topics
Topics must start with a letter or number, can include dashes ('-') and can be up to 35 characters long.
152 lines
4.9 KiB
Plaintext
152 lines
4.9 KiB
Plaintext
;*********************************************************************
|
|
;** **
|
|
;** GSD File for Rosemount 3051 Pressure Transmitter **
|
|
;** Date: 10/30/2018 **
|
|
;** RMT14444.GSD **
|
|
;*********************************************************************
|
|
;
|
|
#Profibus_DP
|
|
GSD_Revision = 5
|
|
Station_Type = 0
|
|
Protocol_Ident = 0
|
|
Vendor_Name = "Rosemount Inc."
|
|
Model_Name = "3051 Pressure Transmitter"
|
|
Revision = "2.0"
|
|
Ident_Number = 0x4444
|
|
Hardware_Release = "5"
|
|
Software_Release = "3.0.0"
|
|
9.6_supp = 1
|
|
19.2_supp = 1
|
|
31.25_supp = 1
|
|
45.45_supp = 1
|
|
93.75_supp = 1
|
|
187.5_supp = 1
|
|
500_supp = 1
|
|
1.5M_supp = 1
|
|
3M_supp = 1
|
|
6M_supp = 1
|
|
12M_supp = 1
|
|
MaxTsdr_9.6 = 60
|
|
MaxTsdr_19.2 = 60
|
|
MaxTsdr_31.25 = 100
|
|
MaxTsdr_45.45 = 250
|
|
MaxTsdr_93.75 = 60
|
|
MaxTsdr_187.5 = 60
|
|
MaxTsdr_500 = 100
|
|
MaxTsdr_1.5M = 150
|
|
MaxTsdr_3M = 250
|
|
MaxTsdr_6M = 450
|
|
MaxTsdr_12M = 800
|
|
Implementation_Type = "RMT ASIC/Hornet"
|
|
Bitmap_Device = "3055555N"
|
|
|
|
;********************************************************************
|
|
;** Slave specific Data **
|
|
;********************************************************************
|
|
Freeze_Mode_supp = 0
|
|
Sync_Mode_supp = 0
|
|
Auto_Baud_supp = 0
|
|
Set_Slave_Add_supp = 1
|
|
Min_Slave_Intervall = 200
|
|
;********************************************************************
|
|
;** User Specific Parameterization -Data **
|
|
;********************************************************************
|
|
;User_Prm_Data_Len = 3
|
|
Max_User_Prm_Data_Len = 8
|
|
|
|
PrmText=1
|
|
Text(0)="Disabled"
|
|
Text(1)="Enabled"
|
|
EndPrmText
|
|
|
|
ExtUserPrmData=1 "Condensed Status"
|
|
Bit(0) 1 0-1 ;PRM_COND
|
|
Prm_Text_Ref=1 ;reference to PrmText
|
|
EndExtUserPrmData
|
|
;The Prm_Structure begins at an offset of three bytes in the User_Prm_Data
|
|
;because DPV1_Status1...3 are transmitted in the first three bytes
|
|
Ext_User_Prm_Data_Const(0) = 0x00, 0x00, 0x08
|
|
Ext_User_Prm_Data_Const(3)=0x05,0x41,0x00,0x00,0x01 ;default values
|
|
;Structure_Length = 5
|
|
;Structure_Type = 65 (profile specific)
|
|
;Slot_Number = 0
|
|
;reserved = 0
|
|
;PRM_COND = 1 (enabled)
|
|
Ext_User_Prm_Data_Ref(7)=1; ;reference to condensed status bit PRM_COND
|
|
Prm_Block_Structure_supp=1 ;enables the block structure of extended parameterization
|
|
|
|
;********************************************************************
|
|
;** extended DP features
|
|
;********************************************************************
|
|
DPV1_Slave = 1
|
|
C2_Read_Write_supp = 1
|
|
C2_Max_Data_Len = 239
|
|
C2_Read_Write_required = 1
|
|
C2_Max_Count_Channels = 2
|
|
Max_Initiate_PDU_Length = 52
|
|
C2_Response_Timeout = 1000
|
|
DPV1_Data_Types = 1
|
|
Ident_Maintenance_supp = 1
|
|
;----------- Description of device related diagnosis: -------------------------
|
|
;
|
|
;Unit_Diag_Bit(16) = "Error Appears"
|
|
;Unit_Diag_Bit(17) = "Error Disappears"
|
|
|
|
Unit_Diag_Bit(35) = "Warmstart"
|
|
Unit_Diag_Bit(36) = "Coldstart"
|
|
;Unit_Diag_Bit(37) = "Maintenance"
|
|
;Unit_Diag_Bit(39) = "Ident_Number Violation"
|
|
Unit_Diag_Bit(40) = "Maintenance Alarm"
|
|
;Unit_Diag_Bit(41) = "Maintenance Demanded"
|
|
Unit_Diag_Bit(42) = "Function Check"
|
|
;Unit_Diag_Bit(43) = "Invalid Process Conditions"
|
|
Unit_Diag_Bit(55) = "Extension Available"
|
|
|
|
;----------- Vendor specific diagnosis: -------------------------
|
|
Unit_Diag_Bit(60) = "Simulate Active"
|
|
;Unit_Diag_Bit(63) = "Other"
|
|
|
|
Unit_Diag_Bit(64) = "Out of Service"
|
|
Unit_Diag_Bit(65) = "Power-Up"
|
|
;Unit_Diag_Bit(66) = "Device Needs Maintenance Now"
|
|
;Unit_Diag_Bit(68) = "Lost NV Data"
|
|
;Unit_Diag_Bit(69) = "Lost Static Data"
|
|
Unit_Diag_Bit(70) = "Memory Failure"
|
|
|
|
;Unit_Diag_Bit(73) = "ROM Integrity Error"
|
|
Unit_Diag_Bit(75) = "NV Memory Integrity Error"
|
|
Unit_Diag_Bit(76) = "Hardware-Software Incompatible"
|
|
;Unit_Diag_Bit(77) = "Man. Block Integrity Error"
|
|
Unit_Diag_Bit(78) = "Sensor Transducer Block Error"
|
|
Unit_Diag_Bit(79) = "LOI malfunction"
|
|
|
|
;********************************************************************
|
|
;** Compact Station **
|
|
;********************************************************************
|
|
Modular_Station = 1
|
|
Max_Module = 1
|
|
Max_Input_Len = 5
|
|
Max_Output_Len = 0
|
|
Max_Data_Len = 5
|
|
Max_Diag_Data_Len = 32
|
|
Slave_Family = 12
|
|
;----------- Module definitions: ----------------------------------------------
|
|
;
|
|
;Modules for Analog Input
|
|
Module = "Analog Input (AI)short" 0x94
|
|
1
|
|
EndModule
|
|
;Modules for Analog Input
|
|
Module = "Analog Input (AI)long" 0x42,0x84,0x08,0x05
|
|
2
|
|
EndModule
|
|
;
|
|
;----------- Description of the module assignment: ----------------------------
|
|
;
|
|
SlotDefinition
|
|
Slot(1) = "Analog Input" 1 1,2
|
|
EndSlotDefinition
|
|
|
|
|
|
|