;** GSD File for Rosemount 3051 Pressure Transmitter **
;** Date: 10/30/2018 **
;** RMT14444.GSD **
;*********************************************************************
;
#Profibus_DP
GSD_Revision = 5
Station_Type = 0
Protocol_Ident = 0
Vendor_Name = "Rosemount Inc."
Model_Name = "3051 Pressure Transmitter"
Revision = "2.0"
Ident_Number = 0x4444
Hardware_Release = "5"
Software_Release = "3.0.0"
9.6_supp = 1
19.2_supp = 1
31.25_supp = 1
45.45_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_31.25 = 100
MaxTsdr_45.45 = 250
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Implementation_Type = "RMT ASIC/Hornet"
Bitmap_Device = "3055555N"
;********************************************************************
;** Slave specific Data **
;********************************************************************
Freeze_Mode_supp = 0
Sync_Mode_supp = 0
Auto_Baud_supp = 0
Set_Slave_Add_supp = 1
Min_Slave_Intervall = 200
;********************************************************************
;** User Specific Parameterization -Data **
;********************************************************************
;User_Prm_Data_Len = 3
Max_User_Prm_Data_Len = 8
PrmText=1
Text(0)="Disabled"
Text(1)="Enabled"
EndPrmText
ExtUserPrmData=1 "Condensed Status"
Bit(0) 1 0-1 ;PRM_COND
Prm_Text_Ref=1 ;reference to PrmText
EndExtUserPrmData
;The Prm_Structure begins at an offset of three bytes in the User_Prm_Data
;because DPV1_Status1...3 are transmitted in the first three bytes
Ext_User_Prm_Data_Const(0) = 0x00, 0x00, 0x08
Ext_User_Prm_Data_Const(3)=0x05,0x41,0x00,0x00,0x01 ;default values
;Structure_Length = 5
;Structure_Type = 65 (profile specific)
;Slot_Number = 0
;reserved = 0
;PRM_COND = 1 (enabled)
Ext_User_Prm_Data_Ref(7)=1; ;reference to condensed status bit PRM_COND
Prm_Block_Structure_supp=1 ;enables the block structure of extended parameterization
;********************************************************************
;** extended DP features
;********************************************************************
DPV1_Slave = 1
C2_Read_Write_supp = 1
C2_Max_Data_Len = 239
C2_Read_Write_required = 1
C2_Max_Count_Channels = 2
Max_Initiate_PDU_Length = 52
C2_Response_Timeout = 1000
DPV1_Data_Types = 1
Ident_Maintenance_supp = 1
;----------- Description of device related diagnosis: -------------------------
;
;Unit_Diag_Bit(16) = "Error Appears"
;Unit_Diag_Bit(17) = "Error Disappears"
Unit_Diag_Bit(35) = "Warmstart"
Unit_Diag_Bit(36) = "Coldstart"
;Unit_Diag_Bit(37) = "Maintenance"
;Unit_Diag_Bit(39) = "Ident_Number Violation"
Unit_Diag_Bit(40) = "Maintenance Alarm"
;Unit_Diag_Bit(41) = "Maintenance Demanded"
Unit_Diag_Bit(42) = "Function Check"
;Unit_Diag_Bit(43) = "Invalid Process Conditions"
Unit_Diag_Bit(55) = "Extension Available"
;----------- Vendor specific diagnosis: -------------------------
Unit_Diag_Bit(60) = "Simulate Active"
;Unit_Diag_Bit(63) = "Other"
Unit_Diag_Bit(64) = "Out of Service"
Unit_Diag_Bit(65) = "Power-Up"
;Unit_Diag_Bit(66) = "Device Needs Maintenance Now"
;Unit_Diag_Bit(68) = "Lost NV Data"
;Unit_Diag_Bit(69) = "Lost Static Data"
Unit_Diag_Bit(70) = "Memory Failure"
;Unit_Diag_Bit(73) = "ROM Integrity Error"
Unit_Diag_Bit(75) = "NV Memory Integrity Error"
Unit_Diag_Bit(76) = "Hardware-Software Incompatible"
;Unit_Diag_Bit(77) = "Man. Block Integrity Error"
Unit_Diag_Bit(78) = "Sensor Transducer Block Error"
Unit_Diag_Bit(79) = "LOI malfunction"
;********************************************************************
;** Compact Station **
;********************************************************************
Modular_Station = 1
Max_Module = 1
Max_Input_Len = 5
Max_Output_Len = 0
Max_Data_Len = 5
Max_Diag_Data_Len = 32
Slave_Family = 12
;----------- Module definitions: ----------------------------------------------
;
;Modules for Analog Input
Module = "Analog Input (AI)short" 0x94
1
EndModule
;Modules for Analog Input
Module = "Analog Input (AI)long" 0x42,0x84,0x08,0x05
2
EndModule
;
;----------- Description of the module assignment: ----------------------------
;
SlotDefinition
Slot(1) = "Analog Input" 1 1,2
EndSlotDefinition