; GSD File for RP1000 PA
|
||
|
; Order-No.:
|
||
|
; File : RKS1183.gsd for AI + TOT
|
||
|
; Updata: for HaiNan J34
|
||
|
; Support Config: AI, AI+TOT
|
||
|
;*******************************************************************
|
||
|
|
||
|
;----- General DP Key Words
|
||
|
#Profibus_DP
|
||
|
GSD_Revision=5
|
||
|
Vendor_Name="ROCKSENSOR"
|
||
|
Model_Name="RP1000 Pressure AI"
|
||
|
Revision="1.8"
|
||
|
Ident_Number=0x1183
|
||
|
Protocol_Ident=0 ; 0 = PROFIBUS-DP
|
||
|
Station_Type=0 ; 0 = DP-Slave
|
||
|
FMS_supp=0
|
||
|
Hardware_Release="V1.0"
|
||
|
Software_Release="V1.2.1"
|
||
|
31.25_supp=1
|
||
|
45.45_supp=1
|
||
|
93.75_supp=1
|
||
|
MaxTsdr_31.25=100
|
||
|
MaxTsdr_45.45=250
|
||
|
MaxTsdr_93.75=1000
|
||
|
Redundancy=0
|
||
|
Repeater_Ctrl_Sig=0
|
||
|
24V_Pins=0
|
||
|
Implementation_Type="SPC42/tmg-itec"
|
||
|
Bitmap_Device="rks1000"
|
||
|
|
||
|
;----- Basic DP-Slave Related Key Words
|
||
|
Freeze_Mode_supp=0
|
||
|
Sync_Mode_supp=0
|
||
|
Set_Slave_Add_supp=1
|
||
|
Fail_Safe=1
|
||
|
Min_Slave_Intervall=200
|
||
|
Modular_Station=1
|
||
|
Max_Module=2
|
||
|
Max_Input_Len=10
|
||
|
Max_Output_Len=2
|
||
|
Max_Data_Len=12
|
||
|
Unit_Diag_Bit(16)="Status appears"
|
||
|
Unit_Diag_Bit(17)="Status disappears"
|
||
|
Unit_Diag_Bit(24)="Hardware failure electronics"
|
||
|
Unit_Diag_Bit(25)="Hardware failure mechanics"
|
||
|
Unit_Diag_Bit(26)="Motor temperature too high"
|
||
|
Unit_Diag_Bit(27)="Electronic temperature too high"
|
||
|
Unit_Diag_Bit(28)="Memory error"
|
||
|
Unit_Diag_Bit(29)="Measurement failure"
|
||
|
Unit_Diag_Bit(30)="Device not initialized"
|
||
|
Unit_Diag_Bit(31)="Device initialization failed"
|
||
|
Unit_Diag_Bit(32)="Zero point error"
|
||
|
Unit_Diag_Bit(33)="Power supply failed"
|
||
|
Unit_Diag_Bit(34)="Configuration invalid"
|
||
|
Unit_Diag_Bit(35)="Restart"
|
||
|
Unit_Diag_Bit(36)="Coldstart"
|
||
|
Unit_Diag_Bit(37)="Maintenance required"
|
||
|
Unit_Diag_Bit(38)="Characteristics invalid"
|
||
|
Unit_Diag_Bit(39)="Ident_Number violation"
|
||
|
Unit_Diag_Bit(55)="Extension available"
|
||
|
|
||
|
;Empty module
|
||
|
Module="No DATA " 0x00
|
||
|
0
|
||
|
EndModule
|
||
|
|
||
|
;AI.OUT
|
||
|
Module="AI Output " 0x94
|
||
|
1
|
||
|
EndModule
|
||
|
|
||
|
;TOT.TOTAL
|
||
|
Module="TOT Counter output " 0x41,0x84,0x85
|
||
|
2
|
||
|
EndModule
|
||
|
|
||
|
Max_Diag_Data_Len=20
|
||
|
Slave_Family=12@RKS
|
||
|
Max_User_Prm_Data_Len = 8
|
||
|
Ext_User_Prm_Data_Const(0) = 0x00,0x00,0x08,0x05,0x41,0x00,0x00,0x01
|
||
|
; DPV1 parameters
|
||
|
; SetPrm is structured
|
||
|
; Structure_Length = 5
|
||
|
; Structure_Type = 65 (profile specific)
|
||
|
; Slot_Number = 0
|
||
|
; reserved = 0
|
||
|
; PRM_COND=1 (enabled)
|
||
|
|
||
|
Prm_Block_Structure_supp = 1
|
||
|
Prm_Block_Structure_req = 0
|
||
|
PrmCmd_supp = 0
|
||
|
PrmCmd_req = 0
|
||
|
Slave_Max_Switch_Over_Time=20 ;=200 ms
|
||
|
Slave_Redundancy_supp=1
|
||
|
Ident_Maintenance_supp=1
|
||
|
|
||
|
;----- Slave related keywords for DP extensions
|
||
|
DPV1_Slave=1
|
||
|
C1_Read_Write_supp=1
|
||
|
C2_Read_Write_supp=1
|
||
|
C1_Max_Data_Len=72
|
||
|
C2_Max_Data_Len=72
|
||
|
C1_Response_Timeout=400
|
||
|
C2_Response_Timeout=400
|
||
|
C1_Read_Write_required=0
|
||
|
C2_Read_Write_required=0
|
||
|
C2_Max_Count_Channels=4
|
||
|
Max_Initiate_PDU_Length=52
|
||
|
Diagnostic_Alarm_supp=0
|
||
|
Process_Alarm_supp=0
|
||
|
Pull_Plug_Alarm_supp=0
|
||
|
Status_Alarm_supp=0
|
||
|
Update_Alarm_supp=0
|
||
|
Manufacturer_Specific_Alarm_supp=0
|
||
|
Extra_Alarm_SAP_supp=0
|
||
|
Alarm_Sequence_Mode_Count=0
|
||
|
Alarm_Type_Mode_supp=0
|
||
|
Diagnostic_Alarm_required=0
|
||
|
Process_Alarm_required=0
|
||
|
Pull_Plug_Alarm_required=0
|
||
|
Status_Alarm_required=0
|
||
|
Update_Alarm_required=0
|
||
|
Manufacturer_Specific_Alarm_required=0
|
||
|
DPV1_Data_Types=0
|
||
|
Check_Cfg_Mode=0
|
||
|
|
||
|
;----- Additional keywords for module assignment
|
||
|
|
||
|
SlotDefinition
|
||
|
Slot(1) = "Analog Input (AI)" 1 0,1
|
||
|
EndSlotDefinition
|
||
|
|